MORLEY ZX1Se User Manual Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 6
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
Electrical ZX1Se ZX2Se ZX5Se
Operating Voltage 230V AC 50Hz (+10%,-15%) 230V AC 50Hz (+10%,-15%) 230V AC 50Hz (+10%,-15%)
Maximum PSU Rating 4.2A total, comprised of 2.5A min @ 25V 8.6A total, comprised of
(panel and loop supply) 1.75A min charger current 2.25A min @ 25V (panel
supply) 2.5A min @
35V (loop supply) 1.66A
min @ 12V (printer supply)
2.2A min charger current
Loop Load 460mA maximum 460mA per loop maximum 460mA per loop maximum
Stand-by Batteries:
Minimum Capacity 2 x 12V 7Ah 2 x 12V 7Ah 2 x 12V 12Ah
Maximum Capacity 2 x 12V 12Ah 2 x 12V 12Ah 2 x 12V 24Ah
Panel Designed to Meet up to max 38Ah
2
up to max 38Ah
2
up to max 38Ah
2&3
EN54-4 Charging
Requirements For Larger
Batteries if Required
Mechanical ZX1Se ZX2Se ZX5Se
Dimensions (mm) 400 x 400 x 135 (H x W x D) 400 x 400 x 135 (H x W x D) 500 x 500 x 195 (H x W x D)
Weight (without batteries) 10 kg 10 kg 20 kg
Colour RAL 9002 - Grey White RAL 9002 - Grey White RAL 9002 - Grey White
Environmental Operating Limits:
Temperature 0ºC to + 40ºC 0ºC to + 40ºC 0ºC to + 40ºC
Humidity 85% non-condensing (max) 85% non-condensing (max) 85% non-condensing (max)
Construction Sheet steel painted, Sheet steel painted, Sheet steel painted,
sealed to IP30 sealed to IP30 sealed to IP30
Cable Entry 14 x 20mm knock-outs in top of cabinet 24 x 20mm knock-outs top
2 x 20mm knock-outs in bottom of cabinet 24 x 20mm knock-outs bottom
400 mm
135 mm
400 mm
400 mm
135 mm
400 mm
500 mm
195 mm
500 mm
Notes
1
Multiple sensor protocols cannot be used in the panel simultaneously. However, different panels on the same network can support different protocols
2
Separate battery box required
3
Please contact your local business manager if there is a requirement to charge batteries >38Ah
* not drawn to scale