MORLEY ZX5Se User Manual Page 4

  • Download
  • Add to my manuals
  • Print
  • Page
    / 6
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 3
ZX1Se ZX2Se ZX5Se
Zones 200 (max) 200 (max) 200 (max)
LED Type Zonal Indicators 20 20 20 (Up to 200 available
FIRE/FAULT/TEXT/DISABLED on special request)
Internal Sounder
User Controls Sound Alarms, Silence/Resound, Mute Buzzer, Accept, System Reset
Programming Controls Alphanumeric multi- Alphanumeric multi- Alphanumeric multi-
level keypad level keypad level keypad
LED Type General Panel FIRE, FAULT, Acknowledged, Disablement, Test, Sounder Fault,
Status Indicators Delayed Mode, Relays Disabled, Earth Fault, System/CPU Fault,
Sounders Disabled, Alarms Silenced, Supply Fault, Power
Serial Interface 2 serial ports with connections for optional RS485 or 3 serial ports with
RS232 plug-in communication cards connections for optional
RS485 or RS232 plug-in
communication cards
Auxiliary Relays 1 fault and 1 re relay voltage free, changeover outputs EN54 format at 1 fault
contacts rated at 24V AC/DC, 1A, 0.6 PF maximum relay and 1 programmable
relay voltage free,
changeover outputs
contacts rated at 24V
AC/DC, 1A, 0.6 pF
maximum
Sounder Outputs 2 programmable outputs. Open and short circuit 4 Programmable outputs.
monitoring. 1A maximum per output Open and short circuit
(Maximum total load 1.3A) monitoring. 1A maximum
per output
(Maximum total load 1.3A)
Hardware Features
Protocol Devices
Each panel is capable of supporting Apollo (Xplorer,
XP95 & Discovery), Hochiki ESP, Nittan, Morley-IAS and
System Sensor protocol devices.
1
ZX1Se Loop Capacity: 1 loop 460mA maximum
ZX2Se Loop Capacity: 1 or 2 loops 460mA per loop
maximum
ZX5Se Loop Capacity: 1 to 5 loops 460mA per loop
maximum
Number Apollo Hochiki System Nittan Morley
of Protocol Protocol Sensor Protocol Protocol
Devices Protocol
126   
198  
Page view 3
1 2 3 4 5 6

Comments to this Manuals