MORLEY-IAS ZXr-A / ZXr-P Repeaters
Page 14 of 16 Document No. 996-144, Revision: 02, Operation & Installation Manual
5 Specifications
Criteria Details
Mechanical
Construction Mild steel sheet enclosure with 3 mounting holes, 5 x 20mm
knockouts in top and 3 x 20mm knockouts in rear wall. All
displays and controls are carried on the enclosure door.
Dimensions 165.0mm (h) x 253.5mm (w) x 50.0mm (d)
Weight 1.7kg approx.
Terminals External connections are made using screw terminals capable of
accepting cable sizes between 0.5mm
2 2
to 2.5mm (14-22AWG).
Environmental
Climatic Classification 3K5, (IEC 721-2-3)
Operating Temperature -5°C to +45°C (recommended +5°C to +35°C)
Humidity 5% to 95% R.H. non condensing
Height above sea level 2000m
Panel Sealing IP30 (EN60529)
-2
Vibration EN60068-2-6, 10-150Hz at 0.981ms (meets the requirements of
EN54-2/4)
EMC Emissions: EN50081-1. Immunity: EN50130-4
Safety EN60950
Electrical
Operating Voltage 18-32V dc
Quiescent Current 60mA @ 24V (Backlight off)
Alarm Current 90mA @ 24V (Backlight on), 100mA @ 18V
Maximum Fault Current Absolute maximum = 600mA.
Resetting thermal fuse – nominal 250mA.
Communications RS485 2-wire serial communications link
Address Range 0, 1-126 (0 is unmonitored)
Controls and Indications
Display 2 x 40 character liquid crystal display (LCD) with back light
illumination
Status Indicators LED Indicators for FIRE, FAULT, DISABLEMENT, ACCEPTED,
SILENCED, COMMUNICATIONS FAILURE and POWER.
Push Buttons Control keys for RESET, MUTE BUZZER, ACCEPT, TEST,
SOUND ALARMS and SILENCE / RESOUND.
Buzzer
Table 4 - ZXr-A / ZXr-P Repeaters Specifications