MORLEY ZX10Se Installation Manual Page 9

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 8
ZXr-A / ZXr-P Repeaters MORLEY-IAS
Operation & Installation Manual Document No. 996-144, Revision: 02, Page 9 of 16
3.4 Address Setting
Set the repeater address in binary using the address switch on the repeater chassis assembly PCB. (See
Figure 9 above).
The address can be set in the range 1 – 126.
It is not necessary to set an address for the ZXr-P (passive) repeater. The address can be set to 0 (all
switch positions OFF). In this mode, the passive repeater will listen to the RS485 communications and will
update its Liquid Crystal Display and LED with the appropriate information. However, if the repeater
becomes disconnected from the RS485 link, the FACP will not report a fault condition.
To report a fault condition at the FACP, in the event that a passive repeater becomes disconnected, set
the passive repeater to an address in the range 1 – 126.
Refer to
Table 1 for address positions.
When commissioned, use the panel ‘Auto-Learn’ function to learn / register the devices installed on the
peripheral loop.
ADDRESS
SWITCH POSITION
SW1:1 SW1:2 SW1:3 SW1:4 SW1:5 SW1:6 SW1:7 SW1:8
1
ON OFF OFF OFF OFF OFF OFF OFF
2
OFF ON OFF OFF OFF OFF OFF OFF
3
ON ON OFF OFF OFF OFF OFF OFF
4
OFF OFF ON OFF OFF OFF OFF OFF
5
ON OFF ON OFF OFF OFF OFF OFF
6
OFF ON ON OFF OFF OFF OFF OFF
7
ON ON ON OFF OFF OFF OFF OFF
8
OFF OFF OFF ON OFF OFF OFF OFF
9
ON OFF OFF ON OFF OFF OFF OFF
10
OFF ON OFF ON OFF OFF OFF OFF
11
ON ON OFF ON OFF OFF OFF OFF
12
OFF OFF ON ON OFF OFF OFF OFF
13
ON OFF ON ON OFF OFF OFF OFF
3
4
5
6
7
8
1
2
ON OFF
14
OFF ON ON ON OFF OFF OFF OFF
15
ON ON ON ON OFF OFF OFF OFF
16
OFF OFF OFF OFF ON OFF OFF OFF
Etc.
126
OFF ON ON ON ON ON ON OFF
Table 1 - Address Switch Settings