ZX Fire Alarm Control Panels MORLEY-IAS
Commissioning Manual Document No. 996-175-000-3, Revision 3 Page 59
16 Supplementary Information
The control panel continually checks the wiring to determine if any external wiring has become short
An indication of an earth fault is given by amber LED Indicators on the panel front. The earth point is
ith a ‘negative’ or ‘positive’ sign on the alphanumeric display.
For example:


16.1 Locating Earth Faults
circuit to earth.
normally maintained at 1V above the battery negative terminal. The polarity of the fault will be
indicated w

ing
Earth faults can appear on the following external cables:
1. S
2 Detector circuit loop wiring
It is also possible to use a dc voltmeter in conjunction with a working panel to find out which circuit is
shorted to earth. This is particularly useful if the fault is past a loop isolator, as this type of fault can
often not be detected by a resistance check at the end of the loop.
The following method describes how to locate this fault by disconnecting the external wiring.
1. Measure the voltage from the battery negative input to the supply board earth input. On a healthy
system, this will read approximately 1V.
2. If the voltage is less than 0.3V, the panel will register an earth fault to negative.
3. If the voltage is more than 1.5V, the panel will register an earth fault to positive.
4. Each of the external cables can be disconnected in turn while monitoring this voltage. As soon as the
faulty wiring is disconnected, the voltage will return to 1V. This identifies which cable is shorted to
earth.
The panel will normally continue to work with a single earth fault on the system. The fault, however,
should be rectified as soon as possible.
Locating the
Earth fault
Most earth faults are found by performing resistance measurements on the cables before connect
them to the panel.
ounder circuit wiring
.
3. Auxiliary 24V output feed.
Please take great care not to disconnect any of the internal board-to-board connections
while the panel is powered up, otherwise damage may be caused to the circuits!