MORLEY ZX2Se User Manual Page 32

  • Download
  • Add to my manuals
  • Print
  • Page
    / 51
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 31
MORLEY-IAS FIRE 6.21 User Manual
Page 32 of 51 Document No 996-140-000-9, Revision: 9 User Manual
Entering values into the cells of the grid alters the settings. Start zone, end zone and time delay are
all numbers; the ringing mode can be selected from a drop-down list:
ZONAL RANGE MODE DELAY TIME (In 10 second increments)
ON N/A
OFF N/A
DOUBLE KNOCK N/A
ZONE DELAY 0 – 1800 secs
OFF/ON ON (1/2 Sensors) 0 – 1800 secs
PULSE ON 0 – 1800 secs
OFF/PULSE ON (1/2 Sensors) 0 – 1800 secs
PULSE/ON ON (1/2 Sensors) 0 – 1800 secs
Any change made can be applied using the buttons on the right hand side of the screen.
EN54
!
The selection of delays longer than 10 minutes (600 secs) does not comply with the
requirements of EN54-2.
4.7.3 Selecting a Ringing Pattern for Editing
To select a ringing pattern number click one in the ringing pattern list at the left of the screen. The
zonal settings for this ringing pattern will appear in the grid, and the grid title should change to:
Details (Pattern N)
Where N is the number of the pattern.
Note: Remember that when a pattern is first created it defaults to a single setting with the mode set to ON
and with no delay selected:
Start Zone End Zone Mode Delay
1 MAXIMUM
(currently 200)
ON 0
4.7.4 Editing a Pattern
4.7.4.1 Adding a Zonal Range Setting
A zonal range can be added by following these simple steps:
1.
Enter the cell for the delay column of the last row of zonal settings.
2. Press the TAB key to create a new empty row.
3. Enter values in the empty row for start zone, end zone, mode and delay.
4.
Use the ‘Add this setting to Pattern’ button for the settings to take effect.
4.7.4.2 Editing a Zonal Range Setting
Follow these steps to change an existing zonal range:
1. Enter the cell of the setting that needs to change.
2.
Make the change (e.g. changing an end zone from 10 to 11).
3.
Use the ‘Add this setting to Pattern’ button for the change to take effect.
Page view 31
1 2 ... 27 28 29 30 31 32 33 34 35 36 37 ... 50 51

Comments to this Manuals