MORLEY ZX2Se User Manual Page 38

  • Download
  • Add to my manuals
  • Print
  • Page
    / 51
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 37
MORLEY-IAS FIRE 6.21 User Manual
Page 38 of 51 Document No 996-140-000-9, Revision: 9 User Manual
4.12.1.4 Allow Remote Evacuation
This setting is only relevant to the hardware key protected ‘dial-up’ facility.
Remote evacuation can only be performed if this option is checked. This is a safety feature, which
prevents accidental evacuation of a remote fire system. This setting applies to the ‘Interactive Panel
Display’.
4.12.2 Linking To a Panel
A physical connection should exist between the panel and computer before an attempt is
made to communicate.
The following actions all begin by attempting to link to a panel.
- Communications|Configure|Panel
- Communications|Configure|PC
- Communications|Retrieve Panel Text
- Communications|Panel Diagnostics
- Communications|Download Event Log
In each case the program will try a number of times to communicate with the panel. If no
communication link can be established then a timeout message will be displayed, e.g.
4.12.3 Configuring a Panel from the PC
Before attempting to configure the panel, check the following:
1. A physical connection exists between the panel and the computer.
2. The memory lock of the panel is in the OPEN position.
3. All devices have been ‘learnt’ using the process described in the ‘Commissioning Manual.
4. The Commission/Configure/PC menu item has been chosen on the panel display.
Once this has been done choose Communications/Configure/Panel and work through the options
displayed on the screen.
Some devices need to be recalibrated after settings have been transferred to the panel.
Therefore, it is recommended that a ‘Calibrate’ is performed after every transfer to panel.
Page view 37