ZX Fire Alarm Control Panel MORLEY-IAS
4 Level 1 Display / Control Functions
At Level 1, the panel operates in a display only mode with the control keys disabled.
If fire alarm or fault conditions exist, the LED Indicators will show these. Detailed information will be
scrolled on the alphanumeric display. Note that the first 4 events will, in turn, be automatically scrolled on
the display – other events can be reached using the manual scroll keys ‘<’ & ‘>’.
The information on the alphanumeric display can be scrolled manually by pressing either the > (forward)
or the < (back) keys.
4.1 Normal Conditions
When the system is in a normal condition, the green AC Power LED will be illuminated. The alphanumeric
display will show the time and date and will alternate between a user programmed text message and a
system status message.
4.2 AC Mains Power Fail Conditions
If the AC Mains power source is interrupted, the AC Power LED will flash. In addition, the internal buzzer
will sound.
The back light illumination of the alphanumeric display will be turned off, the display will show an ‘AC Fail’
message and the Supply Fault LED and Fault LED Indicators will be lit.
If both the AC Mains input and the Battery Standby Input fail then all LED and alphanumeric display
indicators will be off.
The panel will display ‘AC Fail’ together with ‘Battery Fail’ and ‘Charger Fail’ under the
following conditions:
1. When the panel is operating only on batteries that are in good condition; this
gives the
incorrect indication that the batteries are not serviceable.
2. Under very poor battery conditions but with a good mains supply present.
4.3 Fire Alarm Conditions
If the control panel initiates an alarm condition, the FIRE LED Indicators will be illuminated and, if
appropriate, the relevant ZONE FIRE LED Indicators will flash. The internal buzzer will sound and the
alphanumeric display will give detailed information regarding the fire alarm location.
If more than one fire alarm condition is present, the alphanumeric display will either automatically scroll
through or, can be manually scrolled through, the fire alarms registered.
4.3.1 Override Delays
EN54
9
EN54-2 7.11d
Override delays at
Level 1
If the ZX1Se, ZX2Se, ZX5Se and ZX10SE control
panels are configured to operate with delays to
outputs, a manual call point (MCP) will be located
next to the panel.
To override any delays and immediately activate the
bells and other fire alarm output devices, break the
glass in the call point.
BREAK GLASS
Press Here
FIRE
4.4 Fault Conditions
If the panel detects a fault, the FAULT LED is illuminated along with other appropriate system condition
LED Indicators. The alphanumeric display gives detailed information regarding the nature of the fault and
the panel buzzer will sound.
If more than one fault condition is present, the alphanumeric display will either automatically scroll through
or, can be manually scrolled through, the faults registered.
User Manual Document No. 996-182-000-1, Revision 01 Page 7