MORLEY-IAS ZX Fire Alarm Control Panel
Page 8 Document No.996-182-000-1, Revision: 01 User Manual
5 Level 2 Control Functions
All of the functions and operational features described for Level 1 user are available and are the same for
a Level 2 user.
To enable Level 2 operation, press the SHIFT key. The display will then show:
03-Mar-2007 11.38
All devices are within working limits
[Panel ACTIVE Control Keys INHIBITED] [1]
Do you want to enable the control keys ?
Press the YES key and the display will prompt for entry of the password.
03-Mar-2007 11.38
All devices are within working limits
[Panel ACTIVE Control Keys INHIBITED] [1]
Please Enter Password
Enter the 4-digit Level 2 password. The display then shows the Main Menu of user options. The top two
lines of the display momentarily display ‘keypad available for user access’. This is replaced with a
‘SYSTEM NORMAL’ message and details about the loops configured on the panel, unless any panel or
system events exist where details about these are displayed instead.
[ Keypad available for user access ]
-----------------------------------------
[Active] 1)Commission 2)Test 3)Time [1]
4)Enable 5)Disable 6)Print 7)View
If a key has not been pressed for a certain period, the display will revert to the normal Level 1 display
showing the system status message. To re-show the menu display, press the SHIFT key.
If a key has not been pressed for a specified period of time, (normally 5 minutes – programmable), then
‘Level 2’ access will be automatically cancelled. It will be necessary to re-enter the password to re-activate
Level 2 functions.
5.1 Power Failure Condition
5.1.1 AC Mains Power Failure Indication
If the AC Mains input is interrupted, the AC Power LED will flash and the panel buzzer will sound.
The back light illumination of the alphanumeric display will be turned off, the alphanumeric display will
show an ‘AC Fail’ message and the Supply Fault LED Indicator will be lit.
If both the AC Mains input and the Battery Standby Input fail then all LED and alphanumeric display
indicators will be off.
To silence the panel buzzer, press the MUTE BUZZER key.
When MUTED, the buzzer will continue to sound a short beep every 30 seconds. This gives an on-going
warning of the continued AC Mains Failure condition.
When the AC Mains is restored, the AC Power LED returns to steady on.
To clear the latched AC Mains Fault, press the SYSTEM RESET key.