MORLEY-IAS ZX Fire Alarm Control Panel
Page 8 Document No.996-182-000-1, Revision: 01 User Manual
5 Level 2 Control Functions
• All of the functions and operational features described for Level 1 user are available and are the same for
a Level 2 user.
• To enable Level 2 operation, press the SHIFT key. The display will then show:
03-Mar-2007 11.38
All devices are within working limits
[Panel ACTIVE Control Keys INHIBITED] [1]
Do you want to enable the control keys ?
• Press the YES key and the display will prompt for entry of the password.
03-Mar-2007 11.38
All devices are within working limits
[Panel ACTIVE Control Keys INHIBITED] [1]
Please Enter Password
• Enter the 4-digit Level 2 password. The display then shows the Main Menu of user options. The top two
lines of the display momentarily display ‘keypad available for user access’. This is replaced with a
‘SYSTEM NORMAL’ message and details about the loops configured on the panel, unless any panel or
system events exist where details about these are displayed instead.
[ Keypad available for user access ]
-----------------------------------------
[Active] 1)Commission 2)Test 3)Time [1]
4)Enable 5)Disable 6)Print 7)View
• If a key has not been pressed for a certain period, the display will revert to the normal Level 1 display
showing the system status message. To re-show the menu display, press the SHIFT key.
• If a key has not been pressed for a specified period of time, (normally 5 minutes – programmable), then
‘Level 2’ access will be automatically cancelled. It will be necessary to re-enter the password to re-activate
Level 2 functions.
5.1 Power Failure Condition
5.1.1 AC Mains Power Failure Indication
• If the AC Mains input is interrupted, the AC Power LED will flash and the panel buzzer will sound.
• The back light illumination of the alphanumeric display will be turned off, the alphanumeric display will
show an ‘AC Fail’ message and the Supply Fault LED Indicator will be lit.
• If both the AC Mains input and the Battery Standby Input fail then all LED and alphanumeric display
indicators will be off.
• To silence the panel buzzer, press the MUTE BUZZER key.
• When MUTED, the buzzer will continue to sound a short beep every 30 seconds. This gives an on-going
warning of the continued AC Mains Failure condition.
• When the AC Mains is restored, the AC Power LED returns to steady on.
• To clear the latched AC Mains Fault, press the SYSTEM RESET key.