MORLEY-IAS ZX Fire Alarm Control Panel
Page 18 Document No.996-182-000-1, Revision: 01 User Manual
03-Mar-2007 11.38
All devices are within working limits
1)Sounders 2)Relays
ENABLED ENABLED
• The DISABLEMENT and either the SOUNDERS DISABLED or RELAYS DISABLED LED indicators will
be illuminated when the outputs are disabled. A warning message will also be shown on the alphanumeric
display.
• The sounders can only be disabled after confirmation by re-entering the Level 2 password.
5.4.3.6 Enable or Disable Delays
• If the panel has been configured to operate with (pattern) phased evacuation or delays to specific outputs
it is possible to enable or disable these delays.
• Select option “6” from the Enable or Disable menus.
• If disable delays is selected, the display prompts for entry of the Level 2 password to confirm.
03-Mar-2007 11.38
All devices are within working limits
Disable ALL output delays:
Please enter password
• Enter the password.
• The display will briefly show one of the following messages to confirm the action taken before returning to
the menu.
Disable ALL output delays:
Output delays disabled
• If enable delays is selected, the display after a short delay will return to the user main menu. If the panel is
part of a network the following message is displayed for a short period first:
Updating Network, Please wait...
................
5.4.4 Print
• To select the print menu, press ‘6’ from the user main, option menu. The display then shows:
03-Mar-2007 11.38
All devices are within working limits
PRINT : 1)Devices 2)Events 5)Disabled